400 / 401SINGLE DISPLAY CONTROLLER Main features • Universal input configurable from the faceplate • Accuracy better than 0, 2% f.s. at nominal condition • Deviation bargraph indication • Control output: relay or logic with Heat/ Cool function • 1 alarm with configurable function ( up to 3 different alarm setpoints) • Self-tuning, Auto-tuning, Soft-start, Man/ Auto function • Possibility to configure the unit by serial line • Possibility of auxiliary input for current transformer 50mAac or 3rd alarm output, logic or relay ( only 401 mod.) Main applications • Packaging machinery • Goldsmiths’ ovens and machinery • Presses for rubber • Labelling machinery • Food processing plants • Magnetic cards printing machines TECHNICAL DATA INPUTS Accuracy 0, 2% f.s. ± 1digit. Sampling time 120msec. TC - Thermocouple J ( Fe-CuNi) 0...1000° C / 32...1832° F K ( NiCr-Ni) 0...1300° C / 32...2372° F R ( Pt13Rh-Pt) 0...1750° C / 32...3182° F S ( Pt10Rh-Pt) 0...1750° C / 32...3182° F T ( Cu-CuNi) -200...400° C / -328...752° F B ( Pt30Rh-Pt6Rh) 44...1800° C / 111...3272° F E ( NiCr-CuNi) -100...750° C / -148...1382° F N ( NiCrSi-NiSi) 0...1300° C / 32...2372° F RTD 3-wires Pt100 -200...600° C / -328...1112° F PTC ( alternative to RTD) -55...120° C / -67...248° F DC - Linear 0...60mV 12...60mV 0...10V 2...10V 0...20mA 4...20mA Auxiliary input ( only for 401 model) 50mAac, 50/ 60Hz, Ri= 2& OUTPUTS Outputs fully configurable for control and single alarm function, “ OR†or “ AND†. Relay With rating: 5A/ 250Vac, cosÕ = 1 ( order code: R) Logic 10Vdc min. Rout= 100& ( 6V/ 20mA) ( order code: D) POWER SUPPLY Standard: 100...240Vac ± 10% optional: 11...27Vac/ dc ± 10% 50/ 60Hz, max. 10VA